Some settings you want to make to CyberPower's UPS Powerpanel daemon

October 31, 2020

I have a CyberPower UPS and a while back I installed their PowerPanel software to talk to it, in large part to get various status information in an automated way. The other day I discovered that it has some undesirable default settings. So here are some notes on things that you will almost certainly want to change in /etc/pwrstatd.conf if you're using PowerPanel too.

As I discovered, the daemon has at least two undesirable behaviors. It will power off your Linux system one minute after a power failure and then program the UPS to shut down all power ten minutes later, even if line power comes back in the mean time (if line power has come back, it at least turns back on ten seconds later). To disable shutdowns on power failure, the options I am using are:

powerfail-active = no
powerfail-shutdown = no

I suspect that the latter option is sufficient by itself, but the provided script doesn't do very much and I went for overkill. I think these can be set with 'pwrstat -pwrfail -shutdown off' and 'pwrstat -pwrfail -active off', but I edited the configuration file directly (partly because I was already looking at it to find things). There are similar settings for what to do when the battery gets low.

Programming the UPS to power off may only happen if you allow shutdowns on power failure (or general scripts), but I believe that you can specifically turn it off with some additional options:

# The UPS will turn power off when this time
# is expired.
shutdown-sustain = 0

turn-ups-off = no

The former may possibly be set with 'pwrstat -pwrfail -duration 0', but I'm not sure; the pwrstat help text is not clear and I'm not inclined to experiment. I don't think turn-ups-off can be changed through pwrstat. According to the help text comments in pwrstatd.conf, it looks like the equivalent of shutdown-sustain for low battery is the runtime-threshold setting, which also controls how little remaining runtime there is before your system triggers the script and starts shutting down.

My view on automated shutdowns is that if I'm in front of the computer during a power failure, I'm perfectly competent to shut it down when I determine that I need or want to do so. If I'm not in front of the computer, it can quietly run down the battery on its own in the hopes that the outage ends before the battery is exhausted.

As a side note, if you actually have an automated shutdown of your system when the UPS is running low, it's worth thinking about how the system is going to come back up when power returns. PowerPanel's 'have the UPS turn off power (then turn it back on)' has the advantage that it will restart machines that have been shut down, no matter what else happens, provided only that your BIOS is set to always power up when AC power appears (instead of being set to 'last state, whatever that was').

Written on 31 October 2020.
« A sysadmin learning experience courtesy of some UPS issues
A gotcha with combining single-label and multi-label Prometheus metrics »

Page tools: View Source, Add Comment.
Search:
Login: Password:
Atom Syndication: Recent Comments.

Last modified: Sat Oct 31 01:14:57 2020
This dinky wiki is brought to you by the Insane Hackers Guild, Python sub-branch.